Burkert Type 8693 User Manual

Page 117

Advertising
background image

117

Start-up and operation of the

position controller Type 8692

SELEC

OUT DEV.X

EXIT

Lim. DEV.X 1.0%

Selection: Alarm output for excessively large
control deviation of the position controller

OUT BIN 1

ENTER

OUT POS

Output: current position with respect to a specified
limit position

OUT Safepos

Output: actuator in safety position

OUT ERRSP/CMD

Output: sensor break

INPUT

+

-

Lim. DEV.X: 1.0

OK

31)

Input the limit value for the
permitted control deviation
Adjustment range:
1 ... 50 %

32)

Lim. POS 0%

INPUT

+

-

Lim. POS: 0

OK

31)

Input the limit position
Adjustment range:
0 ... 100 %

OUT BIN 1 type

ENTER

SELEC

normally opened

Selection of
switching
signal

EXIT

normally closed

OUT BIN 2

OUT BIN 2 type

OUT remote

Output: operating state MANUAL / AUTOMATIC

Figure 70:

Operating structure OUTPUT-BIN1

Normally closed output, in switched state low (≅→0 V)

Normally opened output, in switched state high (≅→24 V)

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

31)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

32)

The permitted control deviation Lim DEV.X XX must not be less than the dead band.

english

Type 8692, 8693