Start-up and operation of the
position controller Type 8693

25.4. SIG-ERROR -

configuration of signal level fault detection

The

SIG-ERROR function is used to detect a fault on the input signal.

fault detection
Fault detection can be selected at 4 – 20 mA and with a Pt 100 signal.
4 – 20 ma
Fault with input signal ≤→3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)
pt 100
Fault with input signal 225 °C (± 0.5 % of end value, hysteresis 0.5 % of end value)

If other signal types are selected or if process controllers are not activated, the respective menu branch is
hidden. If this configuration does not allow either of the two fault detections,

not available is indicated in

the selection menu.

SIG.ERROR

ENTER

SP/CMD Input

ENTER

EXIT

PV Input

ENTER

Signal fault detection
Process set-point value / nominal
position

Signal fault detection
Process actual value

Figure 100: Operating structure SIG-ERROR-8693