DeviceNet

44.2. static output assemblies

name

Address.of.data.attribute.of.the.assem-
blies.for.read.access..Class,.Instance,.
Attribute

Format.of.the.data.
attribute

INP (factory setting)

4, 21, 3

Byte 0: INP low

Byte 1: INP high

SP

4, 22, 3

Byte 0: SP low

Byte 1: SP high

Table 55:

Static output assemblies

The addresses indicated in the

Static Output Assemblies table can be used to specify a path for the Consumed

Connection Path attribute of an I/O connection, whereby the attributes described in more detail in the following
table can be transferred as output process data via this I/O connection. Nevertheless, by using this address data,
the attributes combined in the assemblies can also be accessed acyclically via

Explicit Messages .

name

Description.of.the.output.data.attributes

Attribute.Address.Class,.
Instance,.Attribute;..
Data.type,.Length

INP

Nominal position

Set-point value of position controller as ‰. Value range 0–1000.
In "pure" position controller mode (

P.CONTRL inactive) the

transfer of the nominal position

INP is required; as a process con-

troller (

PCONTRL active) the transfer of INP is not possible. If the

value is too small or too large, the last valid value is used and is
indicated in

ERR with HEX 14.

111, 1, 58;

UINT, 2 byte

SP

79)

Process set-point value

Set-point value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range –999–9999,

depending on internal scaling.

If the value is too small or too large, the last valid value is used and
is indicated in

ERR with HEX 15.

120, 1, 2;

INT, 2 byte

Table 56:

79)

relevant only for type 8693 and when process controller activated.

english

Type 8692, 8693

Advertising