Error messages on field bus devices – Burkert Type 8693 User Manual

Page 220

Advertising
background image

220

Maintenance and troubleshooting

50.1.4. error messages while the P.TUNE function is running

Display

Causes.of.error

remedial.action

P.TUNE
ERROR 1

No compressed air connected

No change to process variable

Connect compressed air

Check process and, if required, switch on
pump or open the shut-off valve.

Check process sensor.

Table 64:

Error messages P.TUNE, Type 8693

50.1.5. error messages on field bus devices

On.Devicenet

Display

Device.status

Explanation/Troubleshooting

BUS offline

is displayed
approx. every 3
seconds

offline

• Device is not connected to the bus, the network access

procedure (duplicate MAC-ID test, duration approx. 2 s)
has still not ended or device is only active network node

• Baudrate correctly set across network?

• Bus connection including plug assignment correct?

• Power supply and bus connection of the other nodes

correct?

BUS no
connection

is displayed
approx. every 3
seconds

online,

no connection to the master

Device is connected correctly to the bus, the network access
procedure has ended without errors, however there is no
established connection to the master.

BUS
timeout

is displayed
approx. every 3
seconds

I/O connection timeout

An I/O connection is in the

TIME OUT state.

New connection establishment by master; ensure that I/O
data is transferred cyclically or, if

COS confirmed, that cor-

responding Acknowledge messages are sent by the master.

BUS critical
err

is displayed
approx. every 3
seconds

Critical bus error

Other device with the same address in the network or

BUS

OFF due to communication problems.

Change address of the device and restart device

Error analysis in the network with a bus monitor.

Table 65:

Error messages DeviceNet, Type 8693

english

Type 8692, 8693

Advertising
This manual is related to the following products: