19.

iniTial sTarT-up

This section enables you to start up the positioner quickly in order to perform a function check. Additional
functions which are not required are not dealt with in this context.

19.1. safety instructions

danGer!

Danger.–.high.pressure.in.the.equipment!

There is a serious risk of injury when reaching into the equipment.

• Before loosening the lines and valves, turn off the pressure and vent the lines.

WarninG!

Danger.-.improper.installation!

Improper installation may result in injuries as well as damage to the device and the area around it.

• Fluid and electrical installations may be carried out by authorized technicians only and with the appropriate

tools!

Danger.due.to.unintentional.activation.of.the.equipment!

Unintentional activation of the equipment during installation may result in injuries and damage.

• Take appropriate measures to prevent the equipment from being unintentionally activated.

19.2. installation

Before start-up, carry out fluid and electrical installation of the positioner and valve.

When the operating voltage is applied, the positioner is operating and is in the AUTOMATIC operating state.

19.3. specifying the basic settings

The basic settings of the positioner are implemented at the factory.

Before the positioner can undergo a function check, the unit input signal (standard signal) must still be set following
installation of the device and the

X.TUNE function run to adjust the device to local conditions.

To specify the basic settings, switch from the process operating level to the configuration level.

Hold down the left selection key (MENU) for approx. 3 seconds (countdown: two bars converge on the
display).

Then the main menu (MAIN) is indicated on the display together with the menu options which can be individually
marked via the arrow keys and then selected via the right selecion key (ENTER).