Output signals to the control centre (e.g. plc), Supply voltage – Burkert Type 8693 User Manual

Page 69

Advertising
background image

69

Installation

18.3.2. Output signals to the control centre (e.g. plc)

(required for analogue output and/or binary output option
only)

Connect the terminals according to the design (options) of the positioner.

Terminal Configuration

External.circuit

9

8

Analogue position feedback +

Analogue position feedback GND

9

8

GND

+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated

5

6

Binary output 1

Binary output GND

5

6

GND

24 V / 0 V NC / NO

7

6

Binary output 2

Binary output GND

7

6

GND

24 V / 0 V NC / NO

Table 21:

Configuration screw terminals - Output signals to the control centre

18.3.3. supply voltage

Terminal Configuration

External.circuit

14

13

Supply voltage +

Supply voltage GND

14

13

24 V DC ± 10 %max.
residual ripple 10 %

Table 22:

Configuration screw terminals - Supply voltage

When the supply voltage is applied, the positioner is operating.

Now implement the required basic settings and activate automatic adjustment of the positioner as described in
the chapter entitled “19. Initial start-up” or “Starting and setting up the position controller Type 8692”.

english

Type 8692, 8693