18.3.2. Output signals to the control centre (e.g. plc)

(required for analogue output and/or binary output option
only)

→

Connect the terminals according to the design (options) of the positioner.

Terminal Configuration

External.circuit

9

8

Analogue position feedback +

Analogue position feedback GND

9

8

GND

+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated

5

6

Binary output 1

Binary output GND

5

6

GND

24 V / 0 V NC / NO

7

6

Binary output 2

Binary output GND

7

6

GND

24 V / 0 V NC / NO

Table 21:

Configuration screw terminals - Output signals to the control centre

18.3.3. supply voltage

Terminal Configuration

External.circuit

14

13

Supply voltage +

Supply voltage GND

14

13

24 V DC ± 10 %max.
residual ripple 10 %

Table 22:

Configuration screw terminals - Supply voltage

When the supply voltage is applied, the positioner is operating.

→

Now implement the required basic settings and activate automatic adjustment of the positioner as described in
the chapter entitled “19. Initial start-up” or “Starting and setting up the position controller Type 8692”.