PROFIBUS-DP

30.5. process actual value (circular plug m8, 4-pole) -

only Type 8693

Switch
(behind the screw)

1

2

4

3

Process actual value

Circular.plug.M8,.4-pole

Figure 112: Connection - PROFIBUS-DP - Type 8693 - process actual value

Input.type

65)

Pin

Wire.
color

66)

Configuration

Switch

67)

External.circuit

4 – 20 mA
- internally
supplied

1
2
3
4

brown
white
blue
black

+ 24 V transmitter supply
Output from transmitter
GND
Bridge after GND (GND from
3-wire transmitter)

Switch on

left

GND

1
2

3
4

Transmitter

I

4 – 20 mA
- externally
supplied

1
2
3
4

brown
white
blue
black

not assigned
Process actual +
not assigned
Process actual -

Switch on

right

2

4

GND

4 – 20 mA

Frequency
- internally
supplied

1
2
3
4

brown
white
blue
black

+ 24 V sensor supply
Clock input +
Clock input - (GND)
not assigned

Switch on

left

1

2

3

+ 24 V

Clock +

Clock -

Frequency
- externally
supplied

1
2
3
4

brown
white
blue
black

not assigned
Clock input +
Clock input -
not assigned

Switch on

right

2

3

Clock -

Clock +

Pt 100
(see infor-
mation
below)

1
2
3
4

brown
white
blue
black

not assigned
Process actual 1 (current feed)
Process actual 2 (GND)
Process actual 3 (compensation) Switch on

right

Pt 100

2

3
4

Table 44:

Process actual value - Type 8693

For reasons of wire compensation connect the Pt 100 sensor via 3 wires. Always bridge PIN 3 and PIN 4
on the sensor.

65)

Can be adjusted by software (see chapter entitled “20.4. Procedure for specifying the basic settings”)