73

Installation

MENU

INPUT

CMD

MANU

POS
%

XXX

Up arrow key

Description of

configuration of

the keys

Left selection key

Right selection key

Display

Down arrow key

Figure 34:

Description of the control module

An overview of the operating structure of the basic settings can be found in the chapter entitled “19.3.3
Overview of operating structure – Initial start-up” .

19.3.1. setting the input signal (standard signal):

Using the arrow keys, mark the

INPUT menu option in the main menu and then press the right selection key

(ENTER) to enter the

INPUT submenu.

Using the arrow keys, mark the input signal (4 - 20 mA, 0 - 20 mA, ...).

Press the right selection key (SELEC) to select the input signal (dot is marked).

To leave the submenu, press the left selection button (EXIT).

To leave the main menu, press the left selection button (EXIT) again.

You have to leave the main menu by pressing the left selection button (EXIT) before the modified data is
saved in the memory (EEPROM). During the save process the message “

SAVE EEPROM” is indicated on

the display.