PROFIBUS-DP

Then the process data output is input (from the controller to the positioner).

PDO:..Process.Data.Output.
(From the controller to the positioner)

name

Description

Identifier

PDO:CMD
/SP

For.position.controller.Type.8692:

Nominal position (input)

Set-point value of position controller as ‰. Value range 0 – 1000

If the value is too small or too large, the last valid value is used and
is indicated in

ERR with HEX 14.

GSD file:

PDO:CMD/SP

Identifier (HEX): 81, 40, 14

For.process.controller.Type.8693:

Process set-point value (setpoint)

Set-point value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range -999 – 9999,

depending on internal scaling.

If the value is too small or too large, the last valid

value is used and is indicated in

ERR with HEX 14.

PDO:MODE Operating mode (operation mode)

Value range 0 , 1 or 12:

0:

AUTO

12:

BUSSAFEPOS

1:

MANUAL

If the value is too small or too large, the last valid value is used and
is indicated in

ERR with HEX 16.

GSD file:

PDO:MODE

Identifier (HEX): 81, 00, 16

PDO:ERR

Reset error display

If the value > 0,

ERR is reset

GSD file:

PDO:ERR

Identifier (HEX): 81, 00, 17

PDO:
CONact

0: Position controller (8692)

1: Process controller (8693)

GSD file:

PDO:CONact

Identifier (HEX): 81, 00, 19

Table 46:

Process Data Output