X0 - working point of the process controller – Burkert Type 8693 User Manual

Page 134

Advertising
background image

134

Start-up and operation of the
position controller Type 8693

X0 - Working point of the process controller

Operating point in rest state.

Factory setting: 0.0 %

+

-

X0 0.0%

X0 0.0%

INPUT

OK

39)

Adjustment range:
0 – 100 %

Figure 82:

Operating structure P.CONTROL - X0

The "Tables for customer-specific settings”

appendix contains a table "61. Set parameters of the process

controller" in which you can enter your parameters.

FILTER - Filtering of the process actual value input

The filter is valid for all process actual value types and has a low pass behaviour (PT1).

Factory setting: 0

+

-

FILTER 0

FILTER 0

INPUT

OK

39)

Adjustment range:
0 – 9

Figure 83:

Operating structure P.CONTROL - FILTER

Setting.in.10.stages

Setting

Corresponds to limit frequency (Hz)

Effect

0

10

Lowest filter effect

1

5

2

2

3

1

4

0.5

5

0.2

6

0.1

7

0.07

8

0.05

9

0.03

Largest filter effect

Table 34:

Setting of filter effect

39)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english

Type 8692, 8693