46.

cOnfiguraTiOn example 1

The example describes the principle procedure when configuring the device using the software

RSNetWorx for DeviceNet

(Rev. 4.12.00).

46.1. installation of the eds file

The EDS file supplied on the CD is installed with the aid of the EDS Installation Wizard Tool associated with
RSNetWorx.

During the installation procedure the icon also supplied on CD can be assigned (if this does not occur automatically).

46.2. address assignment

There are two options of assigning an address to the devices.

On the one hand the address can be set by pressing the operator keys on the device to the required value within the range
0 – 63 (see chapter entitled

Settings on the positioner), on the other hand the address can be changed from con-

nected devices via the bus with the aid of the Node Commissioning Tool associated with RSNetWorx. Therefore
devices with the default address 63 can also be inserted sequentially into an existing network without difficulty.

“Figure 126: “ indicates how the new address 2 is assigned to a device with address 63.

Figure 126: Screenshot - DeviceNet - Figure 1