Maintenance and troubleshooting

49.1.2. error messages while the X.TUNE function is running

Display

Causes.of.error

remedial.action

X.TUNE locked

The

X.TUNE function is blocked

Input access code

X.TUNE
ERROR 1

No compressed air connected

Connect compressed air

X.TUNE
ERROR 2

Compressed air failed during Autotune Check compressed air supply

X.TUNE
ERROR 3

Actuator or control system deaeration
side leaking

not possible, device defective

X.TUNE
ERROR 4

Control system aeration side leaking

not possible, device defective

X.TUNE
ERROR 6

The end positions for

POS-MIN and

POS-MAX are too close together

Check compressed air supply

X.TUNE
ERROR 7

Incorrect assignment

POS-MIN and

POS-MAX

To determine

POS-MIN and POS-MAX , move

the actuator in the direction indicated on the
display.

Table 59:

Error messages X.TUNE, Type 8692

49.2. Other malfunctions

Problem

Possible.causes

remedial.action

POS = 0 (when CMD > 0 %) or
POS = 100 %, (when CMD < 100 %)

Sealing function (

CUTOFF) has

been unintentionally activated

Deactivate sealing function

Table 60:

Other Malfunctions, Typ 8692