. description.of.the.procedure, Description of the procedure – Burkert Type 8693 User Manual

Page 80

Advertising
background image

80

Start-up and operation of the
position controller Type 8692

20.2. description of the procedure

When the operating voltage has been switched on, the positioner is at the process operating level in the AUTO-
MATIC operating state.

To specify the basic settings, you must switch to the configuration level:

Hold down the left selection key (MENU) for approx. 3 seconds (wait for countdown on display).

Then the main menu is indicated on the display (MAIN).

Press the arrow keys to switch between the main menu options and select a menu option with the right selection key
(ENTER/RUN).

Depending on the function, a menu sub-option or a selection screen is indicated on the display.

Press the arrow keys to switch between these sub-options and select the required settings. Press the right
selection key (SELEC/ENTER) to confirm the selection (the point after the selected parameter is now marked).
Return to the main menu by pressing the left selection key (EXIT).

To save the changed settings, you must leave the configuration level by pressing the left selection key (EXIT).

You are back at the process operating level.

Only when you leave the configuration level by pressing the right selection key, are the changed parameters
and settings saved (

“save EEPROM”).

english

Type 8692, 8693

Advertising
This manual is related to the following products: