Burkert Type 8693 User Manual

Page 132

Advertising
background image

132

Start-up and operation of the
position controller Type 8693

23.6.3. PARAMETER - parameter setting of the process controller

These positioner functions are used to specify the control parameters of the process controller.

The setting can be implemented automatically by means of the

P.TUNE function (see chapter “23.6.6.

P.TUNE - Self-optimization of the process controller (process tune)“).

The basic principles of setting a controller can be found in the chapter entitled "57. Properties of PID
controllers".

DBND - Insensitivity area (dead band) of the process controller

This function causes the process controller to respond from a specific control difference only. This protects both
the solenoid valves in the positioner and the pneumatic actuator.

Factory setting: 1.0 % (with reference to the range of the process actual value scaled by

PV SCALE - PVmin

and

PVmax)

+

-

DBND 1.0%

DBND 1.0%

INPUT

OK

37)

Figure 77:

Operating structure P.CONTROL - DBND

Insensitivity.area.for.process.control

Process set-point
value (SP)

Control
difference

Xd2

Process
actual value
(PV)

Xd2

Xd2‘

Xd2‘

to the
controller

Dead band

Figure 78:

Operating structure P.CONTROL - DBND

37)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english

Type 8692, 8693

Advertising
This manual is related to the following products: