183

PROFIBUS-DP

Address XXX

Input the device address

Press the arrow keys (+/-) to set values from 0 – 126;

Confirm by pressing the selection key on the right (OK).

BUS FAIL

SafePos off

SafePos on

Activate to approach the safety position if the bus communication fails

The position is approached which corresponds to the set-point value last trans-
ferred. (Default setting)

If

SafePos on is set, the following configurations may occur:

• Active

SAFEPOS

menu option If a fault is detected in the bus communication, the drive moves to
the lower

SAFEPOS set position.

• Inactive

SAFEPOS

menu option If a fault is detected in the bus communication, the drive moves to
the end position which it would specify in the isolated state.

BUS PDI

Position

CMD

Process value

70)

Setpoint

70)

Temperature

Operation mode

Errors

P.CONTRL active

71)

Selection of the process values which are to be transferred by the positioner to
the controller (master).

Press the selection key on the right (ENTER) either to activate (x) or deactivate
( ) the respective process value.

For meaning of the process values see table

PDI: Process Data Input.

BUS PDO

CMD / Setpoint

70)

Operation mode

Error reset

P.CONTRL active

71)

Selection of the process values which are to be transferred by the controller
(master) to the positioner.

Press the selection key on the right (ENTER) either to activate (x) or deactivate
( ) the respective process value.

For meaning of the process values see table

PDO: Process Data Output.

70)

only for type 8693 and when process controller activated

71)

only for type 8693

english

Type 8692, 8693