Start-up and operation of the
position controller Type 8692

21.4. manual operating state

Without bar running from left to right along the upper edge of the display.

In MANUAL operating state the valve can be opened or closed manually.

21.4.1. meaning of the keys

key

configuration

description

Left selection key

MENU

Switch to the Configuration level (press for approx. 3 s)

Right selection key

MANU

Switch between the AUTOMATIC (AUTO) or MANUAL (MANU)
operating modes

Up arrow key

OPN

CLS

21)

Aerate the actuator

Control function A (CFA): Valve opens
Control function B (CFB): Valve closes
Control function I (CFI): Connection 2.1 aerated

Down arrow key

CLS

OPN

21)

Deaerate the actuator

Control function A (CFA): Valve closes
Control function B (CFB): Valve opens
Control function I (CFI): Connection 2.2 aerated

Table 28:

MANUAL operating state; Meaning of the keys

CFA: Actuator closes by spring force

CFB: Actuator opens by spring force

CFI: Actuator double-acting

21.4.2. information on the display

After switching to the MANUAL operating state, the display automatically jumps to the actual position (POS) of the
valve actuator.

21)

Only if “Fall” is set in the DIR.ACT auxiliary function