. specifications.of.the.positioner, Conformity, Standards – Burkert Type 8693 User Manual

Page 32: Operating conditions, Mechanical data, Electrical data, Specifications of the positioner

Advertising
background image

32

Description of system

11.3. specifications of the positioner

11.3.1. conformity

In accordance with the EC Declaration of conformity, the positioner Type 8692 and 8693 are compliant with the
EC Directives.

11.3.2. standards

Conformity with the EC Directives is verified by the following standards.

EN 61000-6-3, EN 61000-6-2, EN 61010-1

11.3.3. Operating conditions

caution!

Solar.radiation.and.temperature.fluctuations.may.cause.malfunctions.or.leaks.

• If the device is used outdoors, do not expose it unprotected to the weather conditions.

• Ensure that the permitted ambient temperature does not exceed the maximum value or drop below the mini-

mum value.

Ambient temperature

0 – + 55 °C

Protection class

IP 65 / IP 67 in accordance with EN 60529
(only if cables, plugs and sockets have been connected correctly and in
compliance with the exhaust air concept in chapter “17.3. Pneumatic connection of
the positioner“)

11.3.4. mechanical data

Dimensions

see data sheet

Body material

exterior: PPS, PC, VA, interior: PA 6; ABS

Sealing material

NBR / EPDM

Stroke range of valve spindle 3 – 28 mm

11.3.5. electrical data

Connections

cable gland (24 V DC) or
circular plug-in connector (Profibus DP, DeviceNet, 24 V DC)

Supply voltage

24 V DC ± 10 % max. residual ripple 10 %

Power input

< 5 W

english

Type 8692, 8693

Advertising
This manual is related to the following products: