Process actual value (circular plug m 8, 4 pole) – Burkert Type 8693 User Manual

Page 63

Advertising
background image

63

Installation

17.5.1. process actual value (circular plug m 8, 4 pole)

Input.type

11)

Pin

Wire.
color

12)

Configuration

Switch

External.circuit

4 – 20 mA
- internally
supplied

1

2

3

4

brown

white

blue

black

+ 24 V transmitter supply

Output from transmitter

GND

Bridge after GND (GND from
3-wire transmitter)

Switch

on

left

GND

1
2

3
4

Transmitter

I

4 – 20 mA
- externally
supplied

1

2

3

4

brown

white

blue

black

Not assigned

Process actual +

Not assigned

Process actual -

Switch

on right

2

4

GND

4 – 20 mA

Frequency
- internally
supplied

1

2

3

4

brown

white

blue

black

+ 24 V sensor supply

Clock input +

Clock input - (GND)

Not assigned

Switch

on

left

1

2

3

+ 24 V

Clock +

Clock -

Frequency
- externally
supplied

1

2

3

4

brown

white

blue

black

Not assigned

Clock input +

Clock input -

Not assigned

Switch

on right

2

3

Clock -

Clock +

Pt 100
(see infor-
mation below)

1

2

3

4

brown

white

blue

black

Not assigned

Process actual 1 (current feed)

Process actual 2 (GND)

Process actual 3
(compensation)

Switch

on right

Pt 100

2

3
4

Table 19:

Process actual value

For reasons of wire compensation connect the Pt 100 sensor via 3 wires. Always bridge Pin 3 and Pin 4
on the sensor.

When the supply voltage is applied, the positioner is operating.

Now implement the required basic settings and activate automatic adjustment of the positioner as described
in the chapter entitled “19. Initial start-up” or “Starting and setting up the process controller Type 8693”.

11)

Can be adjusted by software (see chapter entitled “19.3 Specifying the basic settings”)

12)

The indicated colors refer to the connecting cable available as an accessory (918718)