Tn - reset time of the process controller, Tv - hold-back time of the process controller – Burkert Type 8693 User Manual

Page 133

Advertising
background image

133

Start-up and operation of the

position controller Type 8693

KP - Amplification factor of the process controller

The amplification factor specifies the P-contribution of the PID controller.

Factory setting: 1.00

+

KP 1.00

KP 1.00

INPUT

OK

38)

Adjustment range:
0 – 99.99

(% / set unit)

Figure 79:

Operating structure P.CONTROL - KP

The

KP amplification of the process controller refers to the scaled unit.

TN - Reset time of the process controller

Specifies the I-contribution of the PID controller.

Factory setting: 999.9 s

+

TN 999.9

TN 0.5

INPUT

OK

38)

Adjustment range:
0.5 – 999.9 s

Figure 80:

Operating structure P.CONTROL - TN

TV - Hold-back time of the process controller

Specifies the D-contribution of the PID controller.

Factory setting: 0.0 s

+

TV 0.0

TV 0.0

INPUT

OK

38)

Adjustment range:
0 – 999.9 s

Figure 81:

Operating structure P.CONTROL - TV

38)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.