Cal.user calibrating the actual value display, And the inputs for the position set-point value – Burkert Type 8693 User Manual

Page 120

Advertising
background image

120

Start-up and operation of the
position controller Type 8692

22.3.15. CAL.USER

calibrating the actual value display and the inputs for the
position set-point value

The following points can be manually calibrated with this function:

• Position display (

POS) 0 – 100%

• Position set-point value display (

INPUT)

EXIT

calibr. POS

CAL. USER

ENTER

ENTER

OPN

CLS

POS lower 0

EXIT

POS lower 0

INPUT

OK

34)

OPN

CLS

POS upper 0

POS upper 0

INPUT

OK

34)

calibr. INP

ENTER

INP 4mA 0

EXIT

INP 4mA 0

35)

INPUT

OK

34)

INP 20mA 0

INP 20mA 0

35)

INPUT

OK

34)

copyFACT->USER

RUN

Pressfor
approx. 3
seconds

Reset the settings of

CAL.

USER
to factory settings

Figure 71:

Operating structure CAL.USER

Remove the

CAL.USER auxiliary function to re-activate the factory calibration.

34)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

35)

The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).

english

Type 8692, 8693