PROFIBUS-DP

32.

funcTiOnal deviaTiOns frOm The
sTandard mOdel

It is possible to switch between the MANUAL and AUTOMATIC operating states on the process operating level
either via the keyboard on the positioner or via the bus.

It is no longer possible to switch between MANUAL / AUTOMATIC on the keyboard if an operating mode (under
PDO MODE) is transferred to the positioner via the bus.

33.

cOnfiguraTiOn in The prOfiBus-dp
masTer

User parameters (hexparameters) are not required.

33.1. configuration of the process values

Firstly the PDI (Process Data Input) is input (from the positioner to the controller).

PDI:PV and PDI:SP can be selected for Type 8693 (process controller) only and are beneficial only when
process controller activated.

PDI:PCONact can be selected for Type 8693 (process controller) only.