Maintenance and troubleshooting

50.1.2. error messages while the X.TUNE function is running

Display

Causes.of.error

remedial.action

X.TUNE locked

The

X.TUNE function is blocked

Input access code

X.TUNE
ERROR 1

No compressed air connected

Connect compressed air

X.TUNE
ERROR 2

Compressed air failed during Autotune Check compressed air supply

X.TUNE
ERROR 3

Actuator or control system deaeration
side leaking

not possible, device defective

X.TUNE
ERROR 4

Control system aeration side leaking

not possible, device defective

X.TUNE
ERROR 6

The end positions for

POS-MIN and

POS-MAX are too close together

Check compressed air supply

X.TUNE
ERROR 7

Incorrect assignment

POS-MIN and

POS-MAX

To determine

POS-MIN and POS-MAX , move

the actuator in the direction indicated on the
display.

Table 62:

Error messages X.TUNE, Type 8693

50.1.3. error messages while the P.Q‘LIN function is running

Display

Causes.of.error

remedial.action

P.Q LIN
ERROR 1

No compressed air connected

No change to process variable

Connect compressed air

Check process and, if required, switch on
pump or open the shut-off valve.

Check process sensor.

P.Q LIN
ERROR 2

• Current node of the valve stroke was not

reached, as

• Supply pressure failed during

P.Q’LIN

• Autotune was not run.

Check compressed air supply

Run

X.TUNE

Table 63:

Error messages P.Q‘LIN, Type 8693