Start-up and operation of the
position controller Type 8693

25.5. OUTPUT (option) -

configuring the outputs

The

OUTPUT menu option is only indicated in the selection menu of ADD.FUNCTION if the positioner has

outputs (option).

the outputs can be used for the following feedback signals:

Analogue output: Feedback of the current position (

POS), the position set-point value (CMD),

the process actual value (

PV) or the process set-point value (SP) to the control centre.

Binary outputs:

Alarm output for excessively large control deviations of the position controller or

for the output of the current position with respect to a specified limit position (> or <) or

for the output: actuator in safety position or

for the output of a sensor break or

for the output: operating state AUTOMATIC / MANUAL.

the positioner which has the outputs option is available in the following versions:

• one analogue output

• one analogue and two binary outputs

• two binary outputs

According to the version of the positioner only the possible adjustable outputs (

ANALOGUE, ANALOGUE +

BIN 1 + BIN 2 or BIN 1 + BIN 2) are indicated in the OUTPUT menu option.

OUTPUT

OUT ANALOG

OUT BIN2

EXIT

ENTER

ENTER

Configuration of the analogue output

OUT BIN1

Configuration of the binary output 1

Configuration of the binary output 2

Figure 102: Operating structure OUTPUT

english

Type 8692, 8693