203

DeviceNet

Address XXX

Input the device address

Press the arrow keys (+/-) to set values from 0 – 63;

Confirm by pressing the selection key on the right (OK).

BAUDRATE

SafePos off

SafePos on

The baudrate can be changed either by pressing the operator keys on the device or
via the bus. In either case a change has no effect until a reset (send a reset message
to the identity object) or power up is implemented. This means if the changed bau-
drate attribute is accessed before a reset or power up, the read (changed) value does
not agree with the still current baudrate
(to be changed) of the network.

Select 125 kbit/s, 250 kbit/s or 500 kbit/s

BUS FAIL

SafePos off

SafePos on

Activate to approach the safety position if the bus communication fails.

The position is approached which corresponds to the set-point value last transferred.
(Default setting)

If

SafePos on is set, the following configurations may occur:

• Active

SAFEPOS

menu option If a fault is detected in the bus communication, the actuator moves to
the lower

SAFEPOS set position.

• Inactive

SAFEPOS

menu option If a fault is detected in the bus communication, the actuator moves to
the end position which it would specify in the isolated state.

43.

funcTiOnal deviaTiOns frOm The
sTandard mOdel

It is possible to switch between the MANUAL and AUTOMATIC operating states on the process operating level
either via the keyboard on the positioner or via the bus.

It is no longer possible to switch between MANUAL / AUTOMATIC on the keyboard if an operating mode (under
PDO MODE) is transferred to the positioner via the bus.