Start-up and operation of the

position controller Type 8693

pt 100:

calibr. PV

ENTER

PT100 : 0

°C +0000

+

OK

63)

Input new value in °C

Actual value

Figure 107: Operating structure CAL.USER-8693-PV-PT100

An offset value calculated from the actual value and the new value is added to all calculated values.

Press the right selection key (INPUT) to enter the input screen for

Pt 100.

On the display the last digit of the new value is highlighted with a dark background.

Press the up arrow key (+) to specify the individual digits of the value and switch to the next digit with the
down arrow key (←).

When all input values have been specified, confirm by pressing the right selection key (OK) and jump back to
the selection screen.

copy FACTUSER resetting.the.settings.under.CAL.USER.to.the.factory.settings:.....

In the

CAL. USER menu press the arrow keys to select the copy FACTUSER menu option and confirm with

the selection key on the right (ENTER).

Hold down the selection key on the right (RUN) (for approx. 3 seconds) until the countdown has elapsed.

63)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english

Type 8692, 8693