Description of system

7.

Type 8692
pOsiTiOner WiTh pOsiTiOn cOnTrOller

The position measuring system records the current position (

POS) of the pneumatic actuator. The position controller

compares this actual position value with the set-point value (

CMD), which is definable as norm signal. In case of

a control deviation (Xd1), a pulse-width modulated voltage signal is sent to the control system as a manipulated
variable. If there is a positive control difference in single-acting actuators, the air inlet valve is controlled via output
B1. If the control difference is negative, the bleed valve is controlled via output E1. In this way the position of the
actuator is changed until control difference is 0. Z1 represents a disturbance variable.

Valve opening

Continuous
valve

Control system
solenoid valves

Position measuring

Positioner

Position set-
point value

CMD

Xd1

B1

E1

P

K

Z1

POS

position control circuit

+

-

Figure 4:

Signal flow plan of position controller

english