OperaTing levels

The menu structure in the control module of the positioner contains 2 operating levels:

level 1:

operate process

Operating mode

AUTOMATIC

Process / input data displayed

MANUAL

Actuator opened and closed manually

level 2:

parameterization and configuration

Input operating parameters

Supplement the menu with optional menu options

14.1. switching between the operating levels

If AUTOMATIC operating mode has been set when switching from level 1 (Operate process) to level 2
(Parameterization and Configuration), the process continues running while positioner settings are imple-
mented on level 2.

To switch from level 1 (Operate process) to level 2 (Parameterization), press the selection key on the left
(MENU) for approx. 3 seconds. During these 3 seconds (Countdown) 2 bars converge (see “Figure 13”).

To switch back from level 2 (Parameterization and Configuration) to level 1 (Operate process), press the
selection key on the left (EXIT).

MENU

MANU

Press selection key
on left for approx. 3
seconds

2 bars which converge
Countdown

EXIT

ENTER

1

M A I N

ACTUATOR

INPUT
X. TUNE
ADD. FUNCTION

Switch to level 2: Parameterization

Switch back to level 1: Operate process

Press selection key
on left

Figure 13:

Switch operating level