Safepos input the safety position – Burkert Type 8693 User Manual

Page 112

Advertising
background image

112

Start-up and operation of the
position controller Type 8692

22.3.11. SAFEPOS

input the safety position

This function specifies the actuator safety position which is started at defined signals.

The set safety position is only started

• if there is a corresponding signal on the binary input

(Configuration see chapter “21.3.13.

BINARY-IN Activation of the binary input”) or

• if a signal fault occurs

(Configuration see chapter “21.3.12.

SIG-ERROR Configuration of signal level fault detection”).

In the case of the bus version (Profibus / DeviceNet) the safety position is also started with

• corresponding parameter telegram

BUS ERROR (adjustable)

If the mechanical stroke range is limited with the

X.LIMIT function, only safety positions within these limits

can be started.

This function is executed in AUTOMATIC mode only.

Factory setting: 0 %

Safepos

Safepos 0%

EXIT

ENTER

INPUT

+

-

Safepos 0

OK

29)

Input the safety position

Adjustment range:
0...100 %

30)

Figure 65:

Operating structure SAFEPOS

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

29)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

30)

If the safety position is 0 % or 100 %, the actuator is completely deaerated or aerated as soon as the safety
position SIG-ERROR or BINARY-IN is active in the auxiliary functions.