Installation

18.4.1. Terminal assignment when selecting the process actual

value input

Input.type

14)

Switch

15)

Terminal Configuration

External.circuit

4 – 20 mA
- internally
supplied

Switch

on left

1

2

3

4

+ 24 V transmitter input

Transmitter output

Bridge after GND (GND from
3-wire transmitter)

GND

GND

1
2

3
4

Transmitter

I

Frequency
- internally
supplied

1

2

3

4

+ 24 V sensor supply

Clock input +

Not assigned

Clock input - (GND)

1

2

4

+ 24 V

Clock +

Clock - (GND)

4 – 20 mA
- externally
supplied

Switch on

right

1

2

3

4

Not assigned

Process actual +

Process actual -

Not assigned

2

3

GND

+ (4 – 20 mA)

Frequency
- externally
supplied

1

2

3

4

Not assigned

Clock input +

Not assigned

Clock input -

2

4

Clock -

Clock +

Pt 100
(see infor-
mation
below)

1

2

3

4

Not assigned

Process actual 1 (current feed)

Process actual 2
(compensation)

Process actual 3 (GND)

Pt 100

2

3
4

Table 23:

Process actual value input

For reasons of wire compensation connect the Pt 100 sensor via 3 wires.
Always bridge Terminal 3 and Terminal 4 on the sensor.

When the power supply voltage is applied, the positioner is operating.

Now implement the required basic settings and activate automatic adjustment of the positioner as described
in the chapter entitled “19. Initial start-up” or “Starting and setting up the process controller Type 8693”.

14)

Can be adjusted by software (see chapter entitled “19. 3 Specifying the basic settings”)

15)

The switch is situated on the terminal board of the positioner (see “Figure 33”)

english

Type 8692, 8693