. terminating.circuit.for.devicenet.systems, . network.topology.of.a.devicenet.system, Terminating circuit for devicenet systems – Burkert Type 8693 User Manual

Page 199: Network topology of a devicenet system

Advertising
background image

199

DeviceNet

41.6. Terminating circuit for devicenet systems

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct. The circuit prevents
the occurrence of interference caused by signals reflected onto the data lines. The trunk line must be terminated at
both ends with resistors of 120 Ω→each and 1/4 W power loss.

(see “Figure 123: Network topology, DeviceNet”)

41.7. network topology of a devicenet system

Line with one trunk line and several drop lines.

Trunk lines and drop lines consist of identical material (see diagram).

Trunk line
DeviceNet cable

Terminatin-
gresistor
120 Ω →
¼ W

Terminatin-

gresistor

120 Ω →

¼ W

Drop lines
DeviceNet cable,
max. 6 m long

t01

tn

Subscriber 1 (node 1)

Subscriber n (node n)

V +

76)

V –

76)

CAN_H

CAN_L

Figure 123: Network topology, DeviceNet

76)

not assigned, as separate supply voltage

english

Type 8692, 8693