. connection.diagram.type.8693, . supply.voltage.(circular.plug.m12,.4-pole), . bus.connection.(circular.plug.m12,.5-pole) – Burkert Type 8693 User Manual

Page 197: Connection diagram type 8693, Supply voltage (circular plug m12, 4-pole), Bus connection (circular plug m12, 5-pole)

Advertising
background image

197

DeviceNet

41.2. connection diagram Type 8693

Circular.plug.M12,.4-pole

Supply voltage

Switch (behind the screw)

1

2

3

4

1

2

4

3

Process actual value

Circular.plug.M8,.4-pole

Function earth (FE)

Circular.plug.M12,.5-pole

DeviceNet

1

2

3

4

5

Figure 121: Connection of DeviceNet - Type 8693

The supply voltage to the device is not supplied via the DeviceNet voltage V+ und V-, but via the supply
voltage galvanically isolated from the DeviceNet.

41.3. supply voltage (circular plug m12, 4-pole)

PIn

Configuration

External.circuit

1

+ 24 V

1

3

24 V DC ± 10 %
max. residual ripple 10 %

2

not used

3

GND

4

not used

Table 50:

Supply voltage

41.4. Bus connection (circular plug m12, 5-pole)

PIn

Signal

Color

1

Shielding

not used

2

V +

not used

3

V-

not used

4

CAN H

white

5

CAN L

blue

Table 51:

Bus connection