165

Start-up and operation of the

position controller Type 8693

SELEC

OUT DEV.X

EXIT

Lim. DEV.X 1.0%

Selection: Alarm output for excessively large control
deviation of the position controller

OUT BIN 1

ENTER

OUT POS

Output: current position with respect to a specified limit
position

OUT Safepos

Output: drive in safety position

OUT ERR PV

Output: sensor break process actual value

INPUT

+

-

Lim. DEV.X: 1.0

OK

53)

Input the limit value for the
permitted control deviation

Adjustment range: 1 – 50 %

54)

Lim. POS 0%

INPUT

+

-

Lim. POS: 0

OK

53)

Input the limit position

Adjustment range: 0 – 100 %

OUT BIN 1 type

ENTER

SELEC

normally open

Selection of
switching signal

EXIT

normally closed

OUT BIN 2

OUT BIN 2 type

OUT remote

Output: operating state MANUAL / AUTOMATIC

OUT ERRSP/CMD

Output: sensor break process set-point value

Figure 104: Operating structure OUTPUT-BIN1-8693

Normally closed output, in switched state low (≅→0 V)

Normally open output, in switched state high (≅→24 V)

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

53)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

54)

The permitted control deviation Lim DEV.X XX must not be less than the dead band.

english

Type 8692, 8693