. connection.of.the.position.controller.type.8692, Connection of the position controller type 8692 – Burkert Type 8693 User Manual

Page 60

Advertising
background image

60

Installation

17.2. Type 8692 - designation of the circular plug-in

connectors and the contacts

1

2

3

4

5

6

7

8

1

2

3

4

1

2

4

3

Socket.M4,.4-pole

Option: Proximity switch

Circular.plug.M12,.8-pole

Input signals of the control centre
Output signals to the control centre
(option)

Circular.plug.M12,.4-pole

Supply voltage

Figure 28:

Designation of the circular plug-in connectors and contacts 8692

17.3. connection of the position controller Type 8692

17.3.1. input signals of the control centre (e.g. plc) - circular plug

m 12, 8-pole

Pin Wire.color

8)

Configuration

External.circuit./.signal.level

8

red

Set-point value + (0/4 – 20 mA
or 0 – 5 / 10 V)

8

7

GND

+ (0/4 - 20 mA or 0 - 5 / 10 V)
completely galvanically isolated

7

blue

Set-point value GND

1

white

Binary input + (only option)

1

+

0 - 5 V (log. 0)
10 - 30 V (log. 1)

Table 15:

Pin assignment - Input signals of the control centre - circular plug M 12, 8-pole