Start-up and operation of the

position controller Type 8692

22.3.12. SIG-ERROR

configuration of signal level fault detection

The

SIG-ERROR function is used to detect a fault on the input signal.

fault detection
Fault detection can be selected at 4 – 20 mA signal only:
Fault with input signal ≤→3.5 mA (± 0.5 % of final value, hysteresis 0.5 % of final value)

If other signal types are selected, the respective menu branch is hidden. If this configuration does not
allow fault detection,

not available is indicated in the selection menu.

SIG.ERROR

ENTER

SELEC

ERROR off

EXIT

SAFEPOS

Signal fault detection
inactive

Activate approach of
safety position (only pos-
sible if

ERROR on is

selected in the Selection
menu)

SP/CMD Input

ENTER

ERROR on

ENTER

Signal fault detection
active

SELEC

SafePos off

Approach of the safety
position is not active.

SafePos on

Approach of the safety
position is active.
Approach of the safety
position which is saved
in

SAFEPOS.

EXIT

EXIT

Figure 66:

Operating structure SIG-ERROR

If signal fault detection is activated, the respective fault is indicated on the display.
(see chapter entitled "49. Error messages and malfunctions Type 8692")

Safety.position.SAFEPOS on
When

SAFEPOS on is set, the following configurations may occur:

• Active

SAFEPOS menu option

If a fault is detected, the actuator moves to the lower

SAFEPOS set position.

• Inactive menu option

SAFEPOS

If a fault is detected, the actuator moves to the end position which it would specify in the isolated state.

english

Type 8692, 8693