Start-up and operation of the

position controller Type 8692

20.5.4. automatic adjustment (autotune) of the position controller

X.TUNE - Autotune for position controller

WarninG!

Danger.due.to.the.valve.position.changing.when.the.X.TUNE.function.is.running!
When the

X.TUNE is running under operating pressure, there is an acute risk of injury.

• Never run

X.TUNE while a process is running!

• Take appropriate measures to prevent the equipment from being accidentally actuated!

note!

Avoid.maladjustment.of.the.controller.due.to.an.incorrect.pilot.pressure.or.applied.operating.medium.
pressure!

• Run X.TUNE whenever the pilot pressure (= pneumatic auxiliary energy) is available during subsequent

operation.

• Run the X.TUNE function preferably without operating medium pressure to exclude interference caused by

flow forces.

The following functions are actuated automatically:

• Adjustment of the sensor signal to the (physical) stroke of the actuator used

• Determination of parameters for the PWM signals to control the solenoid valves integrated in the positioner

• Adjustment of the controller parameters for the position controller. Optimisation occurs according to the criteria

of a shortest possible correction time with a simultaneous freedom from overshoot.

Procedure:

You start Autotune by selecting

X.TUNE in the main menu (MAIN) using the arrow keys.

Then hold down the right selection key (RUN) for approx. 3 seconds (countdown on display).

When the automatic adjustment completes, the message “

X.TUNE READY

20)

is indicated.

Press any key to return to the main menu.

To stop

X.TUNE, press the left or right selection key (STOP).

20)

If a fault occurs: “TUNE err/break”

english

Type 8692, 8693