Chapter 6: Fastening Instructions

Page 6-12

6.2

Monitoring Functions

The Fusion System is user programmable to select and set the monitoring limits for torque, angle,

time, up to three independent torque rate areas, and special functions describe below.

6.2.1 Peak Torque Monitoring

Torque Monitoring is a continuous process whenever the System is operating. Peak Torque monitor-

ing uses the maximum torque value detected during Fastening.

In Torque Control method, the Peak Torque High and Low Torque limits are set based upon the

engineering specification for the specific fastener.

TORQUE CONTROL

REJECT TYPE

CAUSES

PEAK TORQUE HIGH LIMIT

Re-hit of pre-secured fastener.

Incorrect parameter set-up.

PEAK TORQUE LOW LIMIT

Reject condition caused by another monitor item reject.

FIG. 6-2-1a Peak Torque Monitor – Torque Control








Snug Torque

1

st

Time

Final Time

Standard Torque

Threshold Torque

Speed Change Torque

1

st

Torque

Crossover Torque

Torque

Angle/Time

Peak Torque High Limit

Peak Torque Low Limit