Chapter 4: System Setup and Wiring

Page 4-48

4.15.3 Fieldbus Interfaces – DeviceNet

®

DeviceNet

®

Interface

The DeviceNet communication interface allows slave connection to an industrial DeviceNet net-

work. DeviceNet allows industrial devices to be controlled over an open network architecture

enabling device connection at various locations in the field. This “fieldbus” technology reduces

hard wiring/cabling & provides ease of installation. It uses a broadcast-oriented protocol -the CAN

(Controller Area Network)- that can interface to many devices such as limit switches, sensors, di-

rectional valves, motor starters, bar code readers, process sensors, frequency drives, etc. The

network can have up to 64 nodes.

Maximum I/O data is 512 input bytes & 512 output bytes. FEC Inputs/Outputs are shown in the

following I/O signal map layout.

Note:

The DeviceNet interface is implemented according to the ODVA specification for a commu-

nications adapter (profile no.12). It is acting as a “group two only server” on the DeviceNet net-

work.

FEC integrates the DeviceNet board manufactured by HMS Fieldbus Systems AB into the Multi-

Unit modular I/O board. For further technical information on the DeviceNet interface go to the

HMS website. (

www.hms.se

)

Further DeviceNet information can be found through the Open DeviceNet Vendors Association

(ODVA). (

www.ODVA.org

)

Interface Board with DeviceNet Daughter Board

Item

Description

1

Application Connector

2

DeviceNet Connector

3

Configuration Switches

4

Status LEDs (4)

5

Watchdog LED

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.

Green (flashing @ 2Hz) - module not initialized.

Green (flashing @ 1Hz) - module initialized and running OK.

Red (flashing @ 1Hz) - RAM check fault.

Red (flashing @ 4Hz) - DPRAM check fault.

2

1

3

4

5