FEC FUSIONE-HS-2 User Manual

Page 79

Advertising
background image

FEC FUSION Operations Manual

Chapter 4: System Setup and Wiring (Rev. 2.1)

Page 4-41

Profibus Status LED

Status LEDs

Fieldbus Diagnostics

Red

Indicates faults on fieldbus side

LED #4

Flashing Red -

1sec

Config. Error - in/out length set

at module initialization does not

match length in network config.

Flashing Red -

2sec

Error in user parameter data -

parameter length/content does

not match network

length/content

Flashing Red -

4sec

Error in initialization of Profibus

communication ASIC

On-Line

LED #2

Off

Module not online

Green

Module online and communica-

tion OK

Off- Line

LED #3

Off

Module is not offline

Red

Module is offline on the fieldbus

Note: LED #1- Not Used

Node Address

Before configuring the Profibus-DP module the node address has to be set. This is done with

two rotary switches on the module which can set the node address 1-99 in decimal format.

The Upper rotary switch (closest to the D-sub) sets the “ten” digit (X 10), and the bottom rota-

ry switch sets the single digit. Example: To set node 37, place the “ten” switch on 3, and the

single digit switch on 7.

This switch must be set before power is on, and cannot be changed during operation.

Configuration

FEC Profibus I/O is pre-configured according to the I/O Signal Map (See below). Configura-

tion of the Profibus Master MUST match the configuration of the FEC Profibus slave. In the

Profibus Master set-up, input size and output size is set as “byte” ordering. (Do not use

“word” ordering. This will inverse the I/O location) When setting the Profibus Master configu-

ration, PLC input size refers to FEC output size (ie. Accept, Reject, Busy, etc.) and PLC out-

put size refers to FEC inputs (ie. Start, Stop, Reset, etc.). FEC will show up as 2 modules.

Module 1 is inputs, module 2 is outputs.

Advertising