FEC FUSION Operations Manual

Chapter 4: System Setup and Wiring (Rev. 2.1)

Page 4-45

Termination

Termination of the RIO network requires a terminating resistor at each end of the network. If

this is the last module on the network, turn “ON” the terminating switch located on the inter-

face board.

Specifications

AB Remote I/O Specifications

Speed

57.6, 115, 230K baud - Selectable

Rack Addresses

0-59

Nodes

up to 240 1/4 racks

Rack Configuration supported

1/4

Distance

57.6k - 3048 meter

115K - 1524 meter

230K - 762 meter

Cable

78 ohm Twinax

Belden #9463 or equivalent

Communications Type

Master/Slave

AB Remote I/O connector

Pin 1

COM line

Blue

Pin 2

GND

Shield

Pin 3

COM line

Clear

Status LED

Status LEDs

Error

OFF

Normal Operation

ON - Red

Bus off / Error

Active

OFF

No Communication

ON - Green

Communication Active

Power

OFF

Power Off

ON - Green

Power On