Chapter 4: System Setup and Wiring

Page 4-40

Termination

Termination of the fieldbus requires a terminating resistor at each end of the fieldbus. A ter-

mination switch is provided on the Profibus-DP interface board. Set the switch to “ON”, if

termination is required. If external terminators are used, the switch must be in the off posi-

tion.

GSD File

Each device on a Profibus network is associated with a GSD file containing all necessary in-

formation about the device to be connected. The network configuration program uses this file

during configuration of the network.

The GSD file associated with the FEC device can be downloaded from the FEC website.

www.fec-usa.com

(See Support/Download area) (File : hms_1003.gsd)

(the file can also be downloaded directly from HMS - www.hms.se)

Profibus Specifications

Speed

9.6K - 12M baud – auto-selected

Nodes

126 Note: Node 126 is reserved for

commissioning purposes only

Distance

200m max. at 1.5Mbit/s extendable with

repeaters.

Cable

Shielded Copper Twisted Pair or fiber

optic

Communications Type

Master/Slave - EIA RS485

Protocol Version

Ver. 1.10

Maximum Cyclic I/O Size

244bytes In, 244 bytes out max.

416 total bytes max.

Data transmission

The module only supports cyclic I/O da-

ta transmission.

Note: Limited Coded Binary Integer da-

ta is sent in the cyclic I/O data

Profibus connector - D-Sub

Pin 1

Not Connected

Pin 2

Not Connected

Pin 3

B- Line

Positive RxD/TxD accord-

ing to RS485 Spec.

Pin 4

RTS

Request to send

Pin 5

GND Bus

Isolated GND from RS

485 side

Pin 6

+5V Bus

Isolated +5V from RS 485

side

Pin 7

Not connected

Pin 8

A- Line

Negative RxD/TxD ac-

cording to RS485 Spec.

Pin 9

Not Connected

Housing

Shield

Connected to PE