FEC FUSION Operations Manual

Chapter 4: System Setup and Wiring (Rev. 2.1)

Page 4-3

4.2 Component Dimensions

The specifications for all of the FUSION standard system equipment are outlined in this

Chapter to aid in determining space, mounting & wiring requirements.

4.2.1 CONTROLLER Unit Dimensions

FIG. 4-2-1 Controller Unit Dimensions

Controller weight is 8.6 Kg (18.9lbs.)

The Unit(s) must be mounted with a minimum clearance of 25mm on the left side and 126mm

on the right side to allow for proper heat dissipation. If mounting multiple controllers side by

side you must leave a minimum clearance of 260mm between the units for clearance when

opening the back cover. Programming Cable connections on the front of the Unit require

100mm of clearance. Cable connections on the rear of the Units require 150mm of clearance

below the unit for exiting the Rear cover other than straight down. Controller Units must be

located at a minimum 300mm from any high transient voltage power source. High transient

sources such as relays, AC contactors, AC motor drives, etc. may cause malfunction of the

FUSION Controller unit. All motor cables and I/O cables must be run separate from all high

transient voltage sources. When locating inside an enclosure, avoid mounting at or near the

top where internal enclosure heat is most extreme.

The controller of the FUSION System is designed with 4 mounting holes for easy mounting to

a back panel using standard 6mm screws.