FEC FUSION Operations Manual

4.7

Wiring PLC I/O

All interface devices must accommodate active true low logic for correct operation with

FUSION CONTROLLER

provided for isolated connection to an external controller.

available. Outputs are rated at 12~24 VDC, 200mA. When activated, open collector sink

outputs (normally high) pull the input device signal low (0 VD

and activated when pulled low (0 VDC).

Once wired, the TB1

ing the captive screws located at the top and bottom of the

over to a new controller without disconnecting the terminal wires.

CAUTION

:

The PLC I/O wiring must be routed a minimum of 300 mm away from any transient high vo

tage sources. Cable length must not exceed 50 feet.

DO NOT connect a positive DC

* Output signals shown on terminals A11

SELECT inputs are used, these outputs WILL CHANGE DEFINITION

Select output table

FEC FUSION Operations Manual

Chapter 4: System Setup and Wiring (Rev. 2.1)

Page 4-11

All interface devices must accommodate active true low logic for correct operation with

CONTROLLER Unit DC inputs and outputs (I/O). Four output relay

provided for isolated connection to an external controller. Optional Fieldbus interface

Outputs are rated at 12~24 VDC, 200mA. When activated, open collector sink

outputs (normally high) pull the input device signal low (0 VDC). Inputs are (normally high)

and activated when pulled low (0 VDC).

TB1 terminal block can be quick disconnected from the Controller by

aptive screws located at the top and bottom of the terminal strip, for quick

over to a new controller without disconnecting the terminal wires.

The PLC I/O wiring must be routed a minimum of 300 mm away from any transient high vo

tage sources. Cable length must not exceed 50 feet.

DO NOT connect a positive DC voltage source to the output common.

FIG. 4-7-1 Controller Unit PLC Connector

Output signals shown on terminals A11 – B14 are for BANK 1 signals only. If BANK

SELECT inputs are used, these outputs WILL CHANGE DEFINITION according to the Bank

and the selection of BANK SELECT INPUTS.

Chapter 4: System Setup and Wiring (Rev. 2.1)

All interface devices must accommodate active true low logic for correct operation with the

Four output relay contacts are

ieldbus interfaces are

Outputs are rated at 12~24 VDC, 200mA. When activated, open collector sink

C). Inputs are (normally high)

erminal block can be quick disconnected from the Controller by loosen-

terminal strip, for quick change-

The PLC I/O wiring must be routed a minimum of 300 mm away from any transient high vol-

B14 are for BANK 1 signals only. If BANK

according to the Bank