FEC FUSION Operations Manual

Chapter 4: System Setup and Wiring (Rev. 2.1)

Page 4-51

Configuration Switches

On a DeviceNet network, each node must be assigned its own unique Mac ID. The Mac ID is

a value between 0 and 63 used to identify each node. The Mac ID and Baud Rate are set us-

ing the DIP switches on the front of the module.

These switches must be set before power is on and cannot be changed during opera-

tion.

Baud Rate Settings

Baud Rate

SW-1

SW-2

125K

OFF

OFF

250K

OFF

ON

500K

ON

OFF

Reserved

ON

ON

Mac ID Settings

Mac ID

SW-3

(MSB)

SW-4

SW-5

SW-6

SW-7

SW-8

(LSB)

Address 0

OFF

OFF

OFF

OFF

OFF

OFF

Address 1

OFF

OFF

OFF

OFF

OFF

ON

Address 2

OFF

OFF

OFF

OFF

ON

OFF

Address 3

OFF

OFF

OFF

OFF

ON

ON

…

…

…

…

…

…

…

Address 61

ON

ON

ON

ON

OFF

ON

Address 62

ON

ON

ON

ON

ON

OFF

Address 63

ON

ON

ON

ON

ON

ON

Status LEDs

LED

State

Description

1 - Reserved

-

Reserved for future use.

2 - Network Status

Off

Not Powered / Not Online

Green solid

Link OK, Online, Connected

Green flashing

Online, Not connected

Red solid

Critical Link Failure

Red flashing

Connection Timeout

3 - Module Status

Off

No power to device

Green solid

Device operational

Green flashing

Data size bigger than configured

Red solid

Unrecoverable fault

Red flashing

Minor fault

4 - Reserved

-

Reserved for future use.

ON

8

5

4

2
3

7

6

1

1

2

3

4