Paradyne T1 T1 Access Mux 926x User Manual

Page 160

Advertising
background image

Displaying System Information

7-18

9161-A2-GH30-30

April 1998

Table 7-2.

Health and Status Messages (1 of 5)

Message

What It Indicates

What To Do

System Operational

This message appears when
there are no status messages
to report.

No action needed.

Power Supply Alarm

A power supply or fan tray
problem is detected on the
system.

1. Check that the power

supply or fan tray is
mounted correctly in the
housing.

2. Contact your service

representative.

LOS at Network

n

A Loss of Signal (LOS)
condition is detected on
Network Interface 1 or 2.
Clears when the ratio of ones
to zeros received is greater
than or equal to 12.5%.

1. Network cable problem.

2. No signal is being

transmitted at the far-end
T1 access unit.

3. T1 facility problem.

1. Check that the network

cable is securely attached
at both ends.

2. Check far-end T1 access

unit status.

3. Contact your network

provider.

LOS at DSX

ss-p

A Loss of Signal (LOS)
condition is detected on the
DSX-1 interface in slot

ss,

port

p. Clears when the ratio of

ones to zeros received is
greater than or equal to
12.5%.

1. DSX-1 cable problem.

2. No signal being transmitted

from the DTE.

1. Check that the DSX-1 cable

is securely attached at both
ends.

2. Check the DTE status.

OOF at Network

n

An Out of Frame (OOF)
condition is detected on
Network Interface 1 or 2.

1. Incompatible framing format

between the network and
the T1 access unit.

2. Network cabling problem.

3. T1 facility problem.

1. Check that the framing

format for the network
interface is correct.

2. Check that the network

cable is securely attached
at both ends.

3. Contact your network

provider.