Establishing an online connection – Lenze Engineer v2.21 User Manual

Page 89

Advertising
background image

Lenze · Engineer · 2.13 EN - 10/2014

89

Establishing an online connection

Going online

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.1.9

Gateway Siemens - STEP 7 Communication Server (available by call in STEP 7)

The »Engineer« internally provides a interface for communication purposes via TCI.

Standard procedure - example: PROFIBUS bus system
This section provides information about the basic steps which are required to be able to use the

"STEP 7 Communication Server" bus connection in the »Engineer«.

How to proceed:

1. Create a new project in the »Engineer« including the desired modules, axes and

components.

Getting started: creating a project

( 30)

Note!

To be able to select TCI as bus connection, the »Engineer« must be called from the »STEP

7« software by Siemens.

• That way, the »Engineer« then provides the "STEP 7 Communication Server" bus

connection.

Please assure yourself that the used Siemens PLC supports the TCI function! Further

information is provided e.g. in the Siemens support database.

Components

Version

Controller

Communication module

Technology application

Firmware

Inverter Drives 8400 StateLine

PROFIBUS module

TA - actuating drive speed

03.00.00

1.0

1.0

Servo Drives 9400 HighLine

PROFIBUS module

TA - actuating drive speed

05.00.42

1.0

03.0.3

Software

• Lenze »Engineer«

2.9

• Siemens »STEP 7«

5.4 (SP4)

Note!

The following description refers to the stated versions. Depending on the version,

individual steps of this description may be irrelevant, or additional steps may be

required.