Connecting the Kinetix 6000 Drive System

Chapter 5

Wire the Contactor Enable (CED) Connector

This example applies to any IAM, common-bus leader IAM, or common-bus
follower IAM module.

Figure 51 - IAM Module (CED connector)

Table 66 - Contactor Enable (CED) Connector

CONT EN-

CONT EN+

1 2

Kinetix 6000
IAM Module, Top View

ATTENTION: Wiring the contactor enable relay is required. To avoid personal
injury or damage to the drive, wire the contactor enable relay into your safety
control string. Refer to Contactor Enable Relay on

page 70

.

In common-bus configurations, the contactor enable (CED) connections for
leader and follower drives must be wired in series to the control string.

For interconnect diagrams, refer to Interconnect Diagram Notes beginning on

page 186

.

LIM Module I/O (IOL) Connector or Other Control String

CED Pin

Signal

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

2094-ALxxS, 2094-BLxxS, or
2094-XL75S-Cx
LIM Modules

2094-AL09 and 2094-BL02
LIM Modules

IO_COM1

IO_COM

1

CONT EN-

2.5 (14)

(1)

10 (0.38)

0.5…0.6
(4.4…5.3)

COIL_E2

COIL_A2

2

CONT EN+

(1) The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.