Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

45

Planning the Kinetix 6000 Drive System Installation

Chapter 2

Observe these guidelines when installing your Logix5000 sercos interface
module:

The clean zone (C) is beneath the less noisy modules (I/O, analog,

encoder, registration, an so forth (gray wireway).

The dirty zone (D) is above and below the power supply and noisy

modules (black wireway).

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone.

Figure 18 - Noise Zones (ControlLogix chassis)

Cable Categories for Kinetix 6000 Systems

These tables indicate the zoning requirements of cables connecting to the
Kinetix 6000 drive components.

Table 14 - IAM Module (converter side)

(1)

D

D

C

AC Line

Filter

Spare Slots

Dirty Wireway

Clean Wireway

Route dirty wireways directly above the ControlLogix controller chassis

(shielded by the chassis).

Line Filter/Power Supply

Connections Segregated

(not in wireway)

Dirty I/O

(24V DC I/O, AC I/O)

Clean I/O

(Analog, Encoder

Registration)

Wire/Cable

Connector

Zone

Method

Very
Dirty

Dirty

Clean

Ferrite
Sleeve

Shielded
Cable

CTRL 1 and 2

CPD

X

DC-/DC+ (unshielded cable)

IPD

X

L1, L2, L3 (shielded cable)

X

X

L1, L2, L3 (unshielded cable)

X

CONT EN- and CONT EN+ (M1 contactor)

CED

X

DPI

DPI

X

X