Connector Data and Feature Descriptions

Figure 29 - Enable, Home, and Overtravel Digital Input Circuits

(1) 24V DC source (range) = 21.6V - 26.4V (supplied by drive, not to exceed 250 mA total).
(2) Maximum current input = 10 mA.

Figure 30 - Registration Digital Input Circuits

Sercos Communication Specifications

The Rx and Tx sercos connectors are provided on the Kinetix 6000 IAM and
AM module for communication with the Logix5000 controller.

3k

Ω

0.1

μF

511

Ω

VCC

CTRL_INPUT

IO_COM

IOD-1, -4, -7, -10

IOD-2, -5, -8, -11

IOD-3, -6, -9, -12

1k

Ω

Kinetix 6000
IAM/AM Module

Customer-supplied Input Device

24V DC

I/O SUPPLY

(1)

INPUT

(2)

3k

Ω

511

Ω

VCC

REG_INPUT

INPUT

IO_COM

HCPL-0631

I/O SUPPLY

+24V DC

IOD-13, -16

IOD-14, -17

IOD-15, -18

0.001

μF

1k

Ω

Kinetix 6000
IAM/AM Module

Customer-supplied Registration

Input Device

Attribute

Value

Data rates

4 and 8 Mbps, selectable via DIP switch

(1)

(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting.

Light intensity

Low power or high power, selectable via DIP switch

Cyclic update period

500 μs, min

Node addresses

01…99

(2)

(2) Node address assignments begin with the IAM module. Node addresses for additional axes on the same power rail are assigned by

incrementing from left to right (starting with the IAM module address).
Each IDM unit has it’s own node address switches and can be set to any valid address. However, node addresses for the IAM and AM
modules on the power rail and for IDM units must be unique.