Shunt module status indicators – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 171

Advertising
background image

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

171

Troubleshooting the Kinetix 6000 Drive System

Chapter 7

Shunt Module Status Indicators

Each of the shunt module status indicators provide specific troubleshooting
information.

Table 103 - General Shunt Module Troubleshooting

Module

Status

Under These Conditions

Shunt

Fault is latched.

Until fault condition is corrected and cleared.

Fault is cleared.

Using MASR, MAFR, MGSR instructions or the HIM (red stop button).
Only after the DC bus is discharged (bus status indicator is flashing).
Drive must be configured with 2094-BSP2 shunt module or Bulletin 1394

external shunt module.

IAM/AM

Disabled (for DC bus regulation).

When the 2094-BSP2 shunt module is used on a 230V system.
When either 230V or 460V system is configured with a Bulletin 1394 external

shunt module.

When configured in Common-bus Follower mode.

Enabled to discharge the DC bus.

Drive (IAM or leader IAM module) three-phase power is removed.

Disabled from discharging the
DC bus.

When configured in Common-bus Follower mode.

IMPORTANT

Under some fault conditions, two reset commands can be required to clear
drive and shunt module faults.