Resistive brake modules, Motor brake and thermal switch – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Chapter 2

Planning the Kinetix 6000 Drive System Installation

Resistive Brake Modules

Observe these guidelines when mounting your RBM module:

Mount circuit components and wiring in the dirty zone or in an external

shielded enclosure. If mounting the RBM module in a separate ventilated
shielded enclosure, run wiring inside metal conduit to minimize the effects
of EMI and RFI.

Keep unshielded wiring as short as possible. Keep wiring as flat to the

cabinet as possible.

Route RBM module power and I/O cables separate from other sensitive

low voltage signal cables.

Figure 21 - Noise Zones (RBM mounted above AM module)

Motor Brake and Thermal Switch

The thermal switch and brake are mounted inside the motor, but how you
connect to the axis module depends on the motor series.

Refer to Wire the Motor/Resistive Brake (BC) Connector on

page 111

for

wiring guidelines. Refer to Axis Module/Rotary Motor Wiring Examples
beginning on

page 196

for the interconnect diagram of your drive/motor

combination.

C

D

D

D

VD

D

D

D

C

Line Interface Module

Kinetix 6000
System

Dirty Wireway

Clean Wireway

Motor Power Cables

Very Dirty LIM/IAM Connections

Segregated (not in wireway)

RBM I/O

LIM VAC Input Power

IAM/AM Feedback and

(clean) I/O

LIM and IAM/AM (dirty) I/O

No sensitive

equipment within

150 mm (6.0 in.).

Fiber-optic Cable

Advertising